Skip to main content
Nominal rating @ 25 °C
72 kW (90 kVA)
Frequency
50 Hz
Voltage
400/230 VAC
Passthrough current (genset only)
200 A
Max. combined current (genset+XES)
250 A
Max. load before genset start (fast)
Configurable 57.6 kW - 64.8 kW / delay 0- 30s
Max. load before genset start (slow)
Configurable 54.0 kW - 61.2 kW / delay 60-600s
Overload
1.5 x rated for 30s
Short-circuit current
2 x rated current
Inverter derate @ 30°C
96 %
Inverter derate @ 40°C
90 %
Inverter derate @ 50°C
82 %
Nominal capacity @ 25 °C
127.9 kWh
Typcial charge time @ 25°C
3 hr
Battery chemistry
Lithium iron phosphate (LFP)
Cycle life (80% DoD)
6000 cycles
Maintenance charge interval
<3 weeks
Cooling
Variable speed force air coolingOpen charge
Ingress rating
point IP55 / NEMA 3
Operating temperature range (charge)
0 to +50 °C
Operating temperature range (discharge)
-10 to +50 °C
Dimensions [LxWxH]
2250 x 1398 x 2126 mm
Weight
2800 kg

Details are given for guidance only. Exact equipment may vary according to geographical location and availability.

Nos solutions s’accompagnent d’un large éventail de services standard

Prise en charge

24 h/24 et 7 j/7

Surveillance

à distance

Transport

(livraison sur site)

Ingénierie

en interne

Produits associés

BQ-S 400

CQ-S

CQ-XS 360

Comment pouvons-nous vous aider ?

Démarrer une conversation avec l'un de nos experts

Nous vous invitons à nous faire part de votre défi énergétique afin que nous puissions comprendre votre objectif. Nos experts vous conseilleront et nous développerons ensemble la solution adaptée à vos besoins.

Contactez-nous