Air-to-air heat pump 75
Télécharger
Cooling capacity
1
73.9 kW
Heating capacity
2
46.6 kW
Power Supply (+/- 10%)
400/3/50/PE
Power connection
CEE 125A (5-pole)
Power protection
100 A
EER cooling
2.49 W
COP heating
3.05 W
Air hose connection supply air
800 mm
Air hose connection re-circulation air
800 mm
Air flow
17 600 m³/hr
Remote monitoring
Yes
Max. Starting current
160
Lowest ambient temp. Cooling
0 °C
Lowest ambient temp. Heating
-12 °C
Forklift pockets
Long sides
Transport frame dimensions [LxWxH]
5080 x 2478 x 2081
Full operational weight
3085 kg
Sound pressure @ 10 m
44 dB(A)
Details are given for guidance only. Exact equipment may vary according to geographical location and availability.
1. Cooling capacity based on mixed air: 70% return air 27°C / RH 50% and 30% ambient air 35°C / RH 50%
2. Heating capacity based on mixed air: 70% return air 20°C / RH 50% and 30% ambient air 7°C / RH 87%
Nos solutions s’accompagnent d’un large éventail de services standard
Prise en charge
24 h/24 et 7 j/7
Surveillance
à distance
Transport
(livraison sur site)
Ingénierie
en interne
Comment pouvons-nous vous aider ?
Démarrer une conversation avec l'un de nos experts
Nous vous invitons à nous faire part de votre défi énergétique afin que nous puissions comprendre votre objectif. Nos experts vous conseilleront et nous développerons ensemble la solution adaptée à vos besoins.
Contactez-nous