Cooling capacity (+30 Ambient) 1
108 kW
Heating capacity 2
110 kW
Heating capacity (at -10°C ambient temp)
74 kW
Built-in pump
Yes
Power supply (+/- 10%)
400V/3Ph/50Hz/PE
Power connection
CE125A (5-pole)
Power consumption cool-mode (at +30 ambient, excl. pump)
33 kW
Power consumption heat-mode 2
34 kW
Pump power (Max.)
5.5 kW
Power protection (slow blow fuse)
100 A
EER (Cooling, excl. pump) 1
2.81
COP (Heating, excl. pump) 2
3.24
Hydraulic connections (DIN11851)
80 DN [mm]
Maximum starting current
267 A
Fluid temperature range cooling
-10 / +15 °C
Fluid temperature range heating
+25 / +50 °C
Lowest ambient temp.
-18 °C
Forklift pockets
Yes
Recommended Pon Energy Rental genset size
135 kVA
Dimensions [LxWxH]
3000 x 1235 x 2170 mm
Full operational weight
1895 kg
Sound pressure @ 10m
55 dB(A)

Details are given for guidance only

  1. Based on 12/7°C water temperature, 30°C air ambient
  2. Based on 40/45°C water temperature, 7°C air ambient

The majority of our rental solutions are equipped with remote monitoring.

Nos solutions s’accompagnent d’un large éventail de services standard

Prise en charge

24 h/24 et 7 j/7

Surveillance

à distance

Transport

(livraison sur site)

Ingénierie

en interne

Produits associés

HP300

man next to machine

Comment pouvons-nous vous aider?

Démarrer une conversation avec l'un de nos experts

Nous vous invitons à nous faire part de votre défi énergétique afin que nous puissions comprendre votre objectif. Nos experts vous conseilleront et nous développerons ensemble la solution adaptée à vos besoins.

Contactez-nous