Offshore transformer LV 2200
Specifications
Voltage primary
600/660/690 V
Voltage secondary
400/440/480 V
Current primary
2117 / 1925 / 1840 A
Current secondary
3175 / 2887 / 2646 A
Frequency
50 / 60 Hz
Vector
YNyn0
Cooling
ANAN
Primary switch
2500A / 4 pole
Secondary switch
3200A / 4 pole
Protection
Short circuit, overload and earth-fault
Signals
Fire, Gas, smoke, high temperature, Earth fault
Fire & gas panel
Custom built in Eexed enclosure
Fire extinguishing system
Inergen
Alarms
Gas Low, Gas High, Fire, Common Alarm, Local warning lights
Rig signals
Short circuit, overload and earth-fault
Space heaters
2 ea. 860 W, 230 V, 1~ , 50/60 Hz
Enclosure
10 ft
Wall sockets
2 ea. CEE 32A (5 pole) for 400/440/480V, 2 ea.CEE 16A (3-pole)
Dimensions [LxWxH]
2981 x 2438 x 2735 mm
Weight
9300 kg
Details are given for guidance only
Built according DNV 2.7-1 / EN12079 for Non-hazardous area.