Air-to-air heat pump 75
Télécharger
Cooling capacity
1
73.9 kW
Heating capacity
2
46.6 kW
Power Supply (+/- 10%)
400/3/50/PE
Power connection
CEE 125A (5-pole)
Power protection
100 A
EER cooling
2.49 W
COP heating
3.05 W
Air hose connection supply air
800 mm
Air hose connection re-circulation air
800 mm
Air flow
17 600 m³/hr
Remote monitoring
Yes
Max. Starting current
160
Lowest ambient temp. Cooling
0 °C
Lowest ambient temp. Heating
-12 °C
Forklift pockets
Long sides
Transport frame dimensions [LxWxH]
5080 x 2478 x 2081
Full operational weight
3085 kg
Sound pressure @ 10 m
44 dB(A)
Details are given for guidance only. Exact equipment may vary according to geographical location and availability.