Skip to main content

Air handler 200/460

Télécharger
Cooling capacity 5
200 kW
Heating capacity 6
460 kW
Power supply
400 V/3 Ph/50 Hz/ PE
Power connection
CEE 32A (5-pole)
Power consumption
5.5 kW
Power protection (fuse)
16 A
Max. Air-flow
16500 m³/hr
Hydraulic connections (DIN11851)
80 DN [mm]
Air Inlet (3x) / Outlet (1x) [Ø]
800 / 800 mm
External static pressure
300 Pa
Dimensions [LxWxH]
4000 x 1200 x 2200 mm
Weight
1800 kg
Max. Sound pressure at 10 m
55 dB(A)

Details are given for guidance only. Exact equipment may vary according to
geographical location and availability. 

For specific conditions, contact our application engineers.

1. At water temperatures 7/12°C and air inlet +30°C/50% RH
2. Heating capacity at water temperatures 85/70°C (mixed with 30% PG) and air inlet +10°C/50%RH
3. Max. Sound pressure at 5 m
4. At PG 30% temperatures -8/-5°C and air inlet +3°C/85% RH
5. At water temperatures 6/12°C and air inlet +30°C/65% RH
6. At water temperatures 80/60°C and air inlet -10°C/60% RH

 

Optional/options new airhandler

• Automatic air-valve control
• CO2 sensor and CO2 control (optional)
• Master/slave
• Automatic switch-over (heating/cooling)
• Air filter bags (Standard-Flo SFGS-F7) specific air filter bags on request

 

Nos solutions s’accompagnent d’un large éventail de services standard

Prise en charge

24 h/24 et 7 j/7

Surveillance

à distance

Transport

(livraison sur site)

Ingénierie

en interne

Produits associés

AH50/185

AH100/295

AH200/585

man next to machine

Comment pouvons-nous vous aider ?

Démarrer une conversation avec l'un de nos experts

Nous vous invitons à nous faire part de votre défi énergétique afin que nous puissions comprendre votre objectif. Nos experts vous conseilleront et nous développerons ensemble la solution adaptée à vos besoins