Skip to main content

Specifications

Download

Cooling tower 2000

Cooling capacity 1
1859 kW
Power supply
400V/3Ph/50Hz/PE
Power connection
CEE 63A (5-pole)
Max. Power consumption
31 kW
Power protection (fuse)
63 A
Max. Starting current
1 A
Max. Running current
58 A
Max. Air flow
108000 m3/h
Min. / Max. Fluid flow rate
111 / 320 m3/h
Max. Fluid inlet temperature
45 °C
Hydraulic connections (flanges)
200 / 10 DN / PN
Dimensions [LxWxH]
6605 x 2544 x 2785 mm
Transport weight
4450 kg
Full operational weight
6600 kg
Forklift pockets
Yes
Built-in pump
No
Max. sound pressure level @ 15m
65 dB(A)
Remote monitoring
Yes
Recommended Pon Energy Rental genset size
60 kVA

Details are given for guidance only

  1. Fluid Flow Rate: 320 m3/h, Entering Fluid Temp: 34°C, Leaving Fluid Temp: 29°C, Entering Air Wet Bulb Temp: 21°C

Consult your Pon Energy Rental application engineer for any other operation condition.

Wij bieden de volgende diensten

24/7

support

Remote

monitoring

Transport

(levering op locatie)

Inhouse

engineering

man next to machine

Hoe kunnen we je helpen?

Neem contact met ons op

Deel je uitdagingen en vertel ons wat je wil bereiken. Onze experts denken graag met je mee en bieden advies op maat. Samen creëren we de juiste verhuuroplossing voor elk project.

Contact