Offshore transformer LV 1500
Download
Specifications
Voltage primary
600 / 660 / 690 V
Current primary
1443 / 1312 / 1255 A
Voltage secondary
400 / 440 / 480 V
Current secondary
2165 / 1968 / 1804 A
Frequency
50 / 60 Hz
Vector
YNyn0
Cooling
ANAN
Primary switch
1600 A / 4 pole
Secondary switch
2500 A / 4 pole
Protection
Short circuit, overload and earth-fault
Signals
Fire, gas, smoke, high temperature, earth fault
Fire & gas panel
Custom built in Eexed enclosure
Fire extinguishing system
Light foam. AFFF
Alarms
Gas low, gas high, foam/fire, common alarm, local warning lights
Rig signals
Short circuit, overload and earth-fault
Space heaters
2 ea. 860 W, 230 V, 1~ , 50/60 Hz
Enclosure
10 ft
Wall sockets
2 ea. CEE 32A (5 pole) for 400/440/480V, 2 ea.CEE 16A (3-pole)
Dimensions [LxWxH]
2981 x 2438 x 2735 mm
Weight
8300 kg
Details are given for guidance only
* Built according DNV 2.7-1 / EN12079 for Non-hazardous area.
Wij bieden de volgende diensten
24/7
support
Remote
monitoring
Transport
(levering op locatie)
Inhouse
engineering
Hoe kunnen we je helpen?
Neem contact met ons op
Deel je uitdagingen en vertel ons wat je wil bereiken. Onze experts denken graag met je mee en bieden advies op maat. Samen creëren we de juiste verhuuroplossing voor elk project.
Contact