Skip to main content

Offshore transformer LV 1500

Télécharger

Specifications

Voltage primary
600 / 660 / 690 V
Current primary
1443 / 1312 / 1255 A
Voltage secondary
400 / 440 / 480 V
Current secondary
2165 / 1968 / 1804 A
Frequency
50 / 60 Hz
Vector
YNyn0
Cooling
ANAN
Primary switch
1600 A / 4 pole
Secondary switch
2500 A / 4 pole
Protection
Short circuit, overload and earth-fault
Signals
Fire, gas, smoke, high temperature, earth fault
Fire & gas panel
Custom built in Eexed enclosure
Fire extinguishing system
Light foam. AFFF
Alarms
Gas low, gas high, foam/fire, common alarm, local warning lights
Rig signals
Short circuit, overload and earth-fault
Space heaters
2 ea. 860 W, 230 V, 1~ , 50/60 Hz
Enclosure
10 ft
Wall sockets
2 ea. CEE 32A (5 pole) for 400/440/480V, 2 ea.CEE 16A (3-pole)
Dimensions [LxWxH]
2981 x 2438 x 2735 mm
Weight
8300 kg