Skip to main content

Air handler 200/460

Last ned
Cooling capacity 5
200 kW
Heating capacity 6
460 kW
Power supply
400 V/3 Ph/50 Hz/ PE
Power connection
CEE 32A (5-pole)
Power consumption
5.5 kW
Power protection (fuse)
16 A
Max. Air-flow
16500 m³/hr
Hydraulic connections (DIN11851)
80 DN [mm]
Air Inlet (3x) / Outlet (1x) [Ø]
800 / 800 mm
External static pressure
300 Pa
Dimensions [LxWxH]
4000 x 1200 x 2200 mm
Weight
1800 kg
Max. Sound pressure at 10 m
55 dB(A)

Details are given for guidance only. Exact equipment may vary according to
geographical location and availability. 

For specific conditions, contact our application engineers.

1. At water temperatures 7/12°C and air inlet +30°C/50% RH
2. Heating capacity at water temperatures 85/70°C (mixed with 30% PG) and air inlet +10°C/50%RH
3. Max. Sound pressure at 5 m
4. At PG 30% temperatures -8/-5°C and air inlet +3°C/85% RH
5. At water temperatures 6/12°C and air inlet +30°C/65% RH
6. At water temperatures 80/60°C and air inlet -10°C/60% RH

 

Optional/options new airhandler

• Automatic air-valve control
• CO2 sensor and CO2 control (optional)
• Master/slave
• Automatic switch-over (heating/cooling)
• Air filter bags (Standard-Flo SFGS-F7) specific air filter bags on request

 

Våre tjenester

24/7

support

Fjernovervåking

monitoring

Transport

(delivery on site)

Prosjektberegning

engineering

Relaterte produkter

AH50/185

AH100/295

AH200/585

man next to machine

Hvordan kan vi hjelpe deg?

Start en samtale med oss

Våre strømløsninger oppfyller de høyeste standardene. Vi har produktene du trenger, uansett om du er på utkikk etter hovedstrøm, en pålitelig reserveløsning eller en belastningstest. Vi finner en optimal løsning for din bedrift.