Ventilasjonsanlegg 50 Lav temp.
                                    Last ned                                
                                Specifications
                        Cooling capacity
                                                    4
                                            
                    50 kW
                
                        Heating capacity
                                            
                    N/A
                
                        Power supply
                                            
                    400V/3Ph/50Hz/PE
                
                        Power connection
                                            
                    CEE 63A (5-pole)
                
                        Power consumption
                                            
                    2.5 (27 defrost)
                
                        Power protection (fuse)
                                            
                    63A
                
                        Max. Air flow
                                            
                    25000 m³/hr
                
                        Hydraulic connections (DIN11851)
                                            
                    50 DN [mm]
                
                        Air Inlet / Outlet [Ø]
                                            
                    N/A
                
                         External static pressure
                                            
                    N/A
                
                        Dimensions [LxWxH]
                                            
                    3010 x 1200 x 1200 mm
                
                        Weight
                                            
                    800 kg
                
                        Max. sound pressure @ 5m
                                                    3
                                            
                    67 dB(A)
                Details are given for guidance only. Exact equipment may vary according to geographical location and availability.
For specific conditions, contant our application engineers.
- At water temperatures 7/12°C and air inlet +30°C/50% RH
- Heating capacity at water temperatures 85/70°C (mixed with 30% PG) and air inlet +10°C/50% RH
- Max. Sound Pressure at 5 m
- At PG 30% temperatures -8/-5°C and air inlet +3°C/85% RH
- At water temperatures 6/12°C and air inlet +30°C/65% RH
- At water temperatures 80/60°C and air inlet -10°C/60% RH
 