Chiller EC550
Download
Specifications
Cooling capacity
1
552 kW
Built-in pump
Yes
Power supply
400V/3Ph/50-60Hz/PE
Power connection
M12
Power consumption (at +30 ambient, excl. pump)
155 kW
Pump power (Max.)
18.5 kW
EER (excl. pump) (at +30 ambient)
1
3.56
Power protection (fuse)
400 A
Hydraulic connections (DIN11851)
100 DN [mm]
Maximum starting current
3 A
Fluid temperature range
-12 / +15 °C
Dimensions [LxWxH]
6058 x 2438 x 2438 mm
Weight
7900 kg
Forklift pockets
Yes
Max. sound pressure @ 10m
60 dB(A)
Recommended Pon Energy Rental genset size
250 kVA
Details are given for guidance only
- Cooling capacity based on 12/7°C water temperature, 30°C air ambient.
- Cooling capacity based on 12/7°C water temperature, 35°C air ambient. EUROVENT conditions.
The majority of our rental solutions are equipped with remote monitoring.