Cooling tower 2000

Cooling capacity 1
1859 kW
Power supply
400V/3Ph/50Hz/PE
Power connection
CEE 63A (5-pole)
Max. Power consumption
31 kW
Power protection (fuse)
63 A
Max. Starting current
1 A
Max. Running current
58 A
Max. Air flow
108000 m3/h
Min. / Max. Fluid flow rate
111 / 320 m3/h
Max. Fluid inlet temperature
45 °C
Hydraulic connections (flanges)
200 / 10 DN / PN
Dimensions [LxWxH]
6605 x 2544 x 2785 mm
Transport weight
4450 kg
Full operational weight
6600 kg
Forklift pockets
Yes
Built-in pump
No
Max. sound pressure level @ 15m
65 dB(A)
Remote monitoring
Yes
Recommended Pon Energy Rental genset size
60 kVA

Details are given for guidance only

  1. Fluid Flow Rate: 320 m3/h, Entering Fluid Temp: 34°C, Leaving Fluid Temp: 29°C, Entering Air Wet Bulb Temp: 21°C

Consult your Pon Energy Rental application engineer for any other operation condition.