Air handler 100/295
Download
Specifications
Cooling capacity
1
100 kW
Heating capacity
2
295 kW
Power supply
400V/3Ph/50Hz/PE
Power connection
CEE 32A (5-pole)
Power consumption
8.4 kW
Power protection (fuse)
32 A
Max. Air-Flow
18000 m³/hr
Hydraulic connections (DIN11851)
50 DN [mm]
Air Inlet (3x) / Outlet (1x) [Ø]
800 / 800 mm
External Static Pressure
300 Pa
Dimensions [LxWxH]
3500 x 1200 x 1900 mm
Max. sound pressure @ 10m
62 dB(A)
Weight
1150 kg
Details are given for guidance only. Exact equipment may vary according to
geographical location and availability.
For specific conditions, contact our application engineers.
1. At water temperatures 7/12°C and air inlet +30°C/50% RH
2. Heating capacity at water temperatures 85/70°C (mixed with 30% PG) and air inlet +10°C/50%RH
3. Max. Sound pressure at 5 m
4. At PG 30% temperatures -8/-5°C and air inlet +3°C/85% RH
5. At water temperatures 6/12°C and air inlet +30°C/65% RH
6. At water temperatures 80/60°C and air inlet -10°C/60% RH